It is important to choose the suitable heat conduction medium, to make sure that system works stably. To choose the suitable medium according to the working temperature of the system is essential.
type
|
Temp range℃
|
Heating KW
|
Cooling capacity KW AT ℃
|
Flow/pressure
L/min bar |
Outside size
|
power
KW | ||||||
250
|
100
|
20
|
0
|
-20
|
-40
| |||||||
SUNDI-555WV
|
-45~+300
|
5.5
|
5.5
|
5.5
|
5.5
|
5
|
2.9
|
0.9
|
50
|
2
|
550*680*1450
|
9kw
|
SUNDI-575WV
|
-45~+300
|
7.5
|
7.5
|
7.5
|
7.5
|
7
|
4.2
|
1.5
|
75
|
2
|
550*680*1450
|
11.5kw
|
SUNDI-5A10WV
|
-45~+300
|
10
|
10
|
10
|
10
|
10
|
6
|
2
|
110
|
2.5
|
550*680*1450
|
16kw
|
SUNDI-5A15WV
|
-45~+300
|
15
|
15
|
15
|
15
|
15
|
11
|
3.8
|
110
|
2.5
|
750*750*1850
|
23kw
|
SUNDI-5A25WV
|
-45~+300
|
25
|
25
|
25
|
25
|
25
|
16
|
4.7
|
150
|
2.5
|
1000*950*1750
|
36kw
|
Type
|
SUNDI/UST series
|
Control Mode
|
Feedback PID + Our special dynamic control calculation, Lneya PLC controller
|
Temp.control
|
Material reaction temp.control mode and jacket temp.control mode
|
Program Editor
|
10 programs, each program can edit 45 steps.
|
Communication Portocol
|
MODBUS RTU Protocol,RS485 interface
Optional Ethernet interface/R232 interface
|
Temp.feedback
|
The temperature of three points: the inlet and outlet of heat-conducting medium, material in reactor(External temperature sensor), PT100 sensor
|
Material temp. feedback
|
Material temp. feedback:PT100 or 4~20mA or communication given
Temp.feedback:PT100
|
Temp. difference
|
Set or control oil outlet temp and reactor material temp. difference
Set or control equipment liquid inlet temp. And liquid outlet temp. Difference( keep system safe)
|
Material temp.accuracy
|
±1℃ (sometimes ±0.5℃)
|
Thermal medium temp. accuracy
|
±0.5℃
|
Closed circulation system
|
The whole system is full closed circulation, there is no oil mist at high temperature and no water vapor at low temperature, pressure do not rise up when system is running. The system will supply oil automatically at low temperature.
|
heating
|
Heating max output power
The heater has triple protection and independent temperature limiter to ensure the safety of heating system.
The power is greater than 15KW with a voltage regulator, and the heating power output control adopts 4-20ma linear control.
|
Cooling capacity
|
The power of taking away the heat at different temperature
|
Circulation flow rate and pressure
|
Lower than 75L/min, use Lneya Magnetic pump
Higher than 75L/min use Ultra wide temperature high energy efficiency centrifugal pump.
Pressure selection: 2bar 3bar 5bar 8bar(small power equipment can not customize)
The greater the pressure, the greater the power of the motor, which will increase the system load and reduce the cooling capacity of the system.
|
compressor
|
Different type different brand compress
Mitsubishi, skop, Emerson, Danfoss, Italy Dorin, German blog, bizell, French Tecumseh.
|
evaporator
|
KAORI Plate heat exchanger
|
Oil separator
|
Emerson/Lneya
|
Drying filter
|
danfoss/Emerson
|
Shock tube
|
CASTEL/packless
|
voltage-controlled
|
danfoss/Emerson/fengsheng
|
Expansion valve
|
Emerson thermal expansion valve/Emerson electronic expansion valve/danfoss thermal expansion valve.
Select different expansion valves with different temperature and cooling capacity.
|
Operation panel
|
Lneya 7-inch touch screen,show temp curve\EXCEL data output
Optional Siemens explosion - proof touch screen.(Place the operation panel outside the site area.)
optional GMP, FDA operation and record module (operator use record, data record, alarm record, etc.)
|
Safety protection
|
Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device, liquid low level protection, high temperature protection and temperature fault protection.
|
refrigerant
|
R-404A / R404A R23 mixture/ R404A R23 R14 mixture
|
interface size
|
G1/2、G3/4、G1、DN25 DN32 DN40 DN50 DN65 DN80 DN100(PN10 RF)
|
Water-cooling W
|
With W is water cooled type, lower than -60 degree equipment, you need use 7-25 degree cooled water
|
Water cooled condenser.
|
Tube heat exchanger, plate heat exchanger, tube condenser.
packless、sheng、KAORI、JINDIAN、XIAOLING etc
|
power
|
AC 380V 50HZ Three-phase five-wire system. Small power 220V 50HZ single phase
Optional 460V 60HZ、220V 60HZ three-phase
|
Shell material
|
Standard shellSUS 304,optional spraying plastics (color 7035)
|
Isolation of explosion-proof
|
optioanl(EXdIIBT4)
Lneya explosion-proof product installation license number.:PCEC-2017-B025
|
Positive pressure explosion-proof
|
optioanl(EXPXdmbIICT4) The positive pressure system must be water-cooled type
Lneya explosion-proof product installation license number:PCEC-2017-B025
|
Self pressurizing system
|
Optional self-pressurized 3bar system, the temperature of the system can be expanded, the expansion tank is normal pressure.
KDOC-80 can be used in a pressurized system with a maximum temperature of 250 degrees (-85 degree ~ 250 degree).
KDOC-220 can be used in the self-pressurized system with maximum temperature to 320 degrees (-50 degree ~ 320 degree).
KDOC-210 can be used in a self-pressurized system with a maximum temperature of 300 degrees (-70 degree ~ 300 degree)
|
Flow/pressure
|
Optional flow/pressure sensor, display flow and pressure on the touch screen.
Optional control flow/pressure.
|
One for two system
|
Optional one for two systems: the costis lower than one to one system.
One unit heating and cooling machine contains two circulation system, two cooling system, two heating systems, one expansion system, one electrical system.
|
High exothermic control
|
Customizable high heat control system algorithm and components.
|
flow reactor temperature control module.
|
It can be used in the flow reactor temp control system (pump, internal circulation system, control algorithm, refrigeration)
|
How to Determine Freezing Water Flow Rate?
A lot of people will ask such a question when they buy a cold water machine -- how do you determine the freezing water flow of a refrigerated water unit? So which aspects should we consider the cold water flow?
1. Water pressure test of the unit in and out of the water pipe.
Detect the pressure value of the in- and out-water, then refer to instruction about the water flow under this circumstance and determine whether the water system is normal by looking at the description in the corresponding table or flow diagram of the unit. This difference is also used to determine which part of the water pipeline has a large resistance and make corresponding rectification plan and action.
2. The air inlet temperature of the compressor should be tested only when the refrigeration operation is carried out.
If the temperature of the water chiller is tested lower than zero after running for 30 minutes, then water flow is not enough on water side heat exchanger which causes evaporation temperature and pressure to fall and cause freon in evaporator flow to the compressor suction duct in evaporation heat. That brings about the fact that the compressor suction temperature below zero. In addition, the evaporation pressure and evaporation temperature caused by low temperature setting should be excluded. However, the low-temperature unit can be considered normal as long as there is 6 ~ 8 ℃ overheat of compressor suction. So under normal water flow, the compressor suction temperature generally will be greater than 0 ℃. Temperature lower than this value should be ruled out water system problems.
3. The current needs to be tested when the pump runs.
By detecting the current of the pump of water chiller and comparing with rated current, you can determine the actual water flow, whether its water flow is big or small. Refer to the parameters above, you can draw an exact water system testing analysis report.
A lot of people will ask such a question when they buy a cold water machine -- how do you determine the freezing water flow of a refrigerated water unit? So which aspects should we consider the cold water flow?
1. Water pressure test of the unit in and out of the water pipe.
Detect the pressure value of the in- and out-water, then refer to instruction about the water flow under this circumstance and determine whether the water system is normal by looking at the description in the corresponding table or flow diagram of the unit. This difference is also used to determine which part of the water pipeline has a large resistance and make corresponding rectification plan and action.
2. The air inlet temperature of the compressor should be tested only when the refrigeration operation is carried out.
If the temperature of the water chiller is tested lower than zero after running for 30 minutes, then water flow is not enough on water side heat exchanger which causes evaporation temperature and pressure to fall and cause freon in evaporator flow to the compressor suction duct in evaporation heat. That brings about the fact that the compressor suction temperature below zero. In addition, the evaporation pressure and evaporation temperature caused by low temperature setting should be excluded. However, the low-temperature unit can be considered normal as long as there is 6 ~ 8 ℃ overheat of compressor suction. So under normal water flow, the compressor suction temperature generally will be greater than 0 ℃. Temperature lower than this value should be ruled out water system problems.
3. The current needs to be tested when the pump runs.
By detecting the current of the pump of water chiller and comparing with rated current, you can determine the actual water flow, whether its water flow is big or small. Refer to the parameters above, you can draw an exact water system testing analysis report.
How to Determine Freezing Water Flow Rate?
A lot of people will ask such a question when they buy a cold water machine -- how do you determine the freezing water flow of a refrigerated water unit? So which aspects should we consider the cold water flow?
1. Water pressure test of the unit in and out of the water pipe.
Detect the pressure value of the in- and out-water, then refer to instruction about the water flow under this circumstance and determine whether the water system is normal by looking at the description in the corresponding table or flow diagram of the unit. This difference is also used to determine which part of the water pipeline has a large resistance and make corresponding rectification plan and action.
2. The air inlet temperature of the compressor should be tested only when the refrigeration operation is carried out.
If the temperature of the water chiller is tested lower than zero after running for 30 minutes, then water flow is not enough on water side heat exchanger which causes evaporation temperature and pressure to fall and cause freon in evaporator flow to the compressor suction duct in evaporation heat. That brings about the fact that the compressor suction temperature below zero. In addition, the evaporation pressure and evaporation temperature caused by low temperature setting should be excluded. However, the low-temperature unit can be considered normal as long as there is 6 ~ 8 ℃ overheat of compressor suction. So under normal water flow, the compressor suction temperature generally will be greater than 0 ℃. Temperature lower than this value should be ruled out water system problems.
3. The current needs to be tested when the pump runs.
By detecting the current of the pump of water chiller and comparing with rated current, you can determine the actual water flow, whether its water flow is big or small. Refer to the parameters above, you can draw an exact water system testing analysis report.
A lot of people will ask such a question when they buy a cold water machine -- how do you determine the freezing water flow of a refrigerated water unit? So which aspects should we consider the cold water flow?
1. Water pressure test of the unit in and out of the water pipe.
Detect the pressure value of the in- and out-water, then refer to instruction about the water flow under this circumstance and determine whether the water system is normal by looking at the description in the corresponding table or flow diagram of the unit. This difference is also used to determine which part of the water pipeline has a large resistance and make corresponding rectification plan and action.
2. The air inlet temperature of the compressor should be tested only when the refrigeration operation is carried out.
If the temperature of the water chiller is tested lower than zero after running for 30 minutes, then water flow is not enough on water side heat exchanger which causes evaporation temperature and pressure to fall and cause freon in evaporator flow to the compressor suction duct in evaporation heat. That brings about the fact that the compressor suction temperature below zero. In addition, the evaporation pressure and evaporation temperature caused by low temperature setting should be excluded. However, the low-temperature unit can be considered normal as long as there is 6 ~ 8 ℃ overheat of compressor suction. So under normal water flow, the compressor suction temperature generally will be greater than 0 ℃. Temperature lower than this value should be ruled out water system problems.
3. The current needs to be tested when the pump runs.
By detecting the current of the pump of water chiller and comparing with rated current, you can determine the actual water flow, whether its water flow is big or small. Refer to the parameters above, you can draw an exact water system testing analysis report.
No comments:
Post a Comment