LX -25℃~30℃

Model
LX-0250N
LX-0400N
LX-0700N
LX-1000N
LX-1450N
LX-2000N
LX-2600N
LX-3500N
LX-5000N
Medium temp. range
-15℃30℃
-25℃30℃
-25℃30℃
-25℃30℃
-25℃30℃
-25℃30℃
-25℃30℃
-25℃30℃
-25℃30℃
Temp. Range
ASET multi-function controller, control water tank temperature, temp. accuracy ±0.5℃
Temp. feedback
PT100
Cooling capacity
0℃
1.5KW
2.4KW
4KW
7.5KW
10KW
15.5KW
20kw
26.5kw
38kw
-10℃
1KW
1.5KW
2.7KW
6.3KW
8KW
12KW
15.5kw
21kw
30kw
-20℃

0.8KW
1.5KW
3.5KW
5KW
7.3KW
10kw
13.5kw
20kw
Circulation pump
Max20L/min
Max20L/min
Max35L/min
Max35L/min
Max75L/min
Max75L/min
Max110L/min
Max200L/min
Max250L/min
1.5BAR
1.5BAR
1.5BAR
1.5BAR
2.5BAR
2.5BAR
2.5BAR
2.5BAR
2.5BAR
Volume
15L
17L
25L
30L
40L
60L
80L
150L
300L
Compressor
Tecumseh
Tecumseh
Copeland
Copeland
Copeland
Copeland
Copeland
Copeland
Copeland
Evaporator
Plate heat exchanger
Operation Panel
7-inch color touch screen, record the temperature curve, and export the data in excel format.
Protection
Self-diagnosis function; Overload protection; High pressure switch, overload relay, thermal protection 
device and other security functions.
Refrigerant
R-404A
Connection size
G1/2
G3/4
G3/4
G3/4
G1
G1
G1 1/4
DN40 PN10
DN40 PN10
Dimension
400*600*1150
400*600*1150
500*680*1350
550*680*1450
650*700*1750
750*750*1950
750*750*1950
950*1700*2050
1000*2000*2200
Weight Air-cooled
115KG
145kg
180kg
225kg
290kg
340kg
400kg
650kg
950kg
Power (max)
AC220V
AC220V
AC220V
AC380V
AC380V
AC380V
AC380V
AC380V
AC380V
50hz
1.5kW
2.2kW
3kW
4kW
5kW
6kW
8 kW
12kW
17kW
Case material
Cold rolled steel
Optional
SUS304 case material
Optional
220V 60HZ 3 phases460V 60HZ 3 phases

The outdoor installation of air-cooled chillers make it easy to be affected by outdoor sunlight, and  the ventilation and the environment and space has a direct impact on the cooling effect of the chiller. The common failure and processing method are as follows:

(1) Frequent start and stop of the compressor: there may be too much or too little refrigerant, resulting in pressure protection switch action which is resulted from too high exhaust pressure or  too low suction pressure, and also poor water system circulation make sevaporator surface frost.

Method: When the refrigerant is too much, the extra can be released at the vent. If there is a shortage, check whether there are leaks of the fluorine and fill the refrigerant.

If the water circulation system is blocked or stored in the air, you should exhaust; if water circulation too small, utilize the open refrigeration water circulation system.

(2) Noisy compressor when running: check whether the expansion valve fails, the temperature package discharges the suction pipe from the compressor, which causes the liquid refrigerant return to the compressor. If it is damaged, it should be repaired, for example, if the compressor is damaged, it should be replaced.

(3) Poor refrigeration capacity: the cause of the poor refrigeration capacity may be the insufficient refrigerant and low evaporation temperature that makes the por cooling effect of the pipeline; poor heat dissipation of the condenser; too large the resistant of the water circulation system,etc..

The refrigerant pipe should be checked for leakage and fill the refrigerant after repairing.You should repair the insulation layer and Clean the condenser to check whether the fan is working properly as well as clean the pipe filter.

The outdoor installation of air-cooled chillers make it easy to be affected by outdoor sunlight, and  the ventilation and the environment and space has a direct impact on the cooling effect of the chiller. The common failure and processing method are as follows:

(1) Frequent start and stop of the compressor: there may be too much or too little refrigerant, resulting in pressure protection switch action which is resulted from too high exhaust pressure or  too low suction pressure, and also poor water system circulation make sevaporator surface frost.

Method: When the refrigerant is too much, the extra can be released at the vent. If there is a shortage, check whether there are leaks of the fluorine and fill the refrigerant.

If the water circulation system is blocked or stored in the air, you should exhaust; if water circulation too small, utilize the open refrigeration water circulation system.

(2) Noisy compressor when running: check whether the expansion valve fails, the temperature package discharges the suction pipe from the compressor, which causes the liquid refrigerant return to the compressor. If it is damaged, it should be repaired, for example, if the compressor is damaged, it should be replaced.

(3) Poor refrigeration capacity: the cause of the poor refrigeration capacity may be the insufficient refrigerant and low evaporation temperature that makes the por cooling effect of the pipeline; poor heat dissipation of the condenser; too large the resistant of the water circulation system,etc..

The refrigerant pipe should be checked for leakage and fill the refrigerant after repairing.You should repair the insulation layer and Clean the condenser to check whether the fan is working properly as well as clean the pipe filter.